Skip to main content

HOME HVACR F-Gas Compliance

F-Gas Compliance

European F-Gas regulations stipulate a step-wise decrease in HFC use of 79% by 2030, ahead of the Kigali Amendment goal for 2047. The overall aim is to reduce and contain refrigerant emissions by adopting responsible refrigeration. As such, it is a criminal offense to release F-gases into the atmosphere, with the responsibility for the legislation falls on the owners and operators to:

  • Prevent leakage
  • Ensure that leak checks are carried out
  • Repair any leaks as soon as possible
  • Arrange proper refrigerant recovery
  • Maintain record of any refrigerant losses, additions and servicing

The requirement for leak detection, inspection and leak check frequency depends on the total CO2 equivalent (tCO2e) charge of the equipment. This can be calculated from a quantity of F-Gas by multiplying the mass of the gas (in tons), by the GWP of the gas. The mass of the F-Gas is usually expressed in kilograms (kg) on product labels. To convert the mass to tons, divide by 1,000. As the following table shows, stationary equipment that has over 5 tCO2e requires regular inspection and calibration. Inspections can cut in half if using a calibrated refrigerant leak detection system (ALDS). Bearing in mind, ALDS is mandatory for refrigeration systems over 500 tCO2e. For instance, inspection time for a system with 400 tCO2e is every 6 months. However, with an ALDS, inspection frequency is every 12 months.

Size of Equipment Leak Detection Requirement Leak Detection System (ALDS) Inspection / Calibration Frequency Equipment Leak Check Frequency (without ALDS) Equipment Leak Check Frequency (with ALDS)
0–5 tCO2e
Optional
Optional
Optional
Optional
5–50 tCO2e
Optional
12-months
12-months
24-months
50–500 tCO2e
Optional
12-months
6-months
12-months
500+ tCO2e
Required
12-months
N/A
6-months

Bacharach provide a number of low-level refrigerant monitoring solutions for F-Gas compliance. The Multi-Zone and Single-Zone fixed refrigerant monitors, the PGM-IR portable refrigerant monitor along with the cloud based Parasense Refrigerant Tracking and Compliance software.

Top Products


Multi-Zone Gas Monitor

Bacharach’s Multi-Zone Gas Monitor delivers the best refrigerant leak detection available, with industry-leading MDL of 1ppm for halogenated gases, the fastest sampling frequency and the widest range of refrigerants accurately detected. The large graphic LCD display and LED status indicators provide a system-wide overview at a glance.

Learn more

Single-Zone Refrigerant Monitor

Precision monitoring for low-level refrigerant leak detection for small to medium size facilities.

Learn more

PGM-IR Portable Refrigerant Monitor

The PGM-IR portable refrigerant monitor offers superior performance and functionality for low ppm level leak detection of refrigerants, Carbon Dioxide, Nitrous Oxide or Sulfur Hexafluoride. A built-in library of 60+ refrigerants enables the PGM-IR to accurately detect the smallest leaks at their source. The unit is immune to sudden changes in temperature or humidity and to over-exposure. The PGM-IR requires no zeroing of positive readings with extended exposure to gas. It has a data logging capacity of up to 200 readings.

Learn more