I cannot discover the Gateway on my BACnet MSTP System.
a. Check that the Network Number on the Gateway is unique.
b. Verify the Baud Rate on the Gateway configuration page.
c. If using a ProtoNode Gateway, switch to the “Single-Node’ Profile BACnet/IP
Can I change the BACnet UDP port from 47808 to another value?
Yes, this can be changed in the config.csv file. Please reference Section 5.1 in the BACnet IP driver manual to see how to set this parameter.
I can discover the points from the Gateway on the BMS, but they are all marked as “Unreliable” or there is no data associated with the points.
The field device that is configured on the Client-Side of your Gateway is probably not communicating. Please check the Connection Overview
Does my Multiport Gateway come pre-configured?
The Multiport Gateway does not come pre-configured by default. The Multiport will contain an example configuration file that will include the drivers that were ordered. This configuration will need to be expanded to match the application. MSA offers a Custom Configuration Service where our Configuration Engineers can build the config.csv which can then be emailed or pre-loaded before shipping. Please contact your Regional Sales Manager for more information.
How do I configure Protocol X to Protocol Y?
Please contact MSA Technical support at smc-support@msasafety.com and list the protocols that you are trying to convert. Our Technical Support Engineers will provide a sample config.csv file.
My Multiport Gateway seems to work for a day or a few weeks and then suddenly stops.
Your Multiport Gateway may have a corrupted license file or has exceeded the point count license on it. Please take a diagnostic capture of your Multiport Gateway and send it to technical support at smc-support@msasafety.com.
My Multiport Gateway has crashed, how can I recover it?
How can I calculate the number of license data points my configuration file is using?
Please reference the following Enote to see how the Gateway calculates the data points.
Can I simulate my config.csv file without having to download it to the gateway?
My Multiport Gateway is showing an error “Unit is in Recovery Mode”. How can I fix this?
Recovery Mode occurs when an internal Module of the Multiport Gateway firmware has suffered a crash or corruption. A firmware upgrade will be required to resolve.
i. Take a Diagnostic Capture and Contact Technical Support.
- Download and install the FieldServer Toolbox.
- Connect to the Gateway’s Ethernet port
- Hit the Diagnostic button on the FieldServer Toolbox
- Take a 5-minute, Full Diagnostic of the Gateway
- Email the zip file to smc-support@msasafety.com. Be sure to include your observations and what you would like Technical Support to check.
How can I check if my field device is communicating to the Gateway?
a. Check the Graphical User Interface
- Download and install the FieldServer Toolbox.
- Connect to the Gateway’s Ethernet port
- Use the toolbox to connect to the Gateway
- On the Navigation Tree, navigate to View->Connections
- Check the Tx Msg and Rx Msg columns for the Protocol. If both columns are incrementing, then the Gateway is communicating to the field device.
b. Take a Diagnostic Capture and Contact Technical Support
- Download and install the FieldServer Toolbox.
- Connect to the Gateway’s Ethernet port
- Hit the Diagnostic button on the FieldServer Toolbox
- Take a 5-minute, Full Diagnostic of the Gateway
- Email the zip file to smc-support@msasafety.com. Be sure to include your observations and what you would like Technical Support to check.